RP00036/1 MOQ: 1

Yodal Alarm  03 24Vdc

P.O.A
Mounting: The Y03 series alarm should be mounted to a reasonably flat wall or bulkhead of suitable material using the lugs projecting from the side of the case. The lugs are bored 6mm clearance on 102mm centres. The minimum recommended length of fixing screws is 25mm. To maintain the integrity of the weather seal, the cable must be fitted using a suitable sealed gland. Line monitoring (DC only) excludes additional voltage options - 3-wire 2-stage or 2-wire single-stage, monitor via reverse polarity - 2-wire 2-stage i.e. bi-polar inputs, monitor via threshold (applied voltage<1V) End of line resistor Minimum 3K3 ohm 0.5 watts, wire-wound or metal film type Technical Specification •Operating temperature: -25 to + 55 C • Relative humidity: 90% @ 40 C • Sound output: 100dB(A) @ 1 meter • IP54 rated standard • Volume control allowing 18dB(A) adjustment • Minimum current consumption 20mA • Optional independent 2nd stage via second DIL switch Main Features •2-stage alarm • 3-wire polarised DC (Not additional voltage option) & AC, or 2-wire bi-polar for DC only • 3-wire AC second stage control • Complies with BS 5839 • Flame retardant ABS plastic enclosure • Stainless steel fixings • Continuously rated • 32 selectable tones meeting international regulations • Sound selection via 5 way DIL switch

Supplied As Each
Contact Us For Price